Dual-Lite LPS35-T 35W Central Lighting Micro Inverter, Recessed Ceilig T-Grid Mount
Designed for indoor installation in commercial or industrial applications, LIGHTPOWER™ Series micro inverter systems provide sinusoidal Emergency AC power to lighting fixtures equipped with incandescent, linear fluorescent, compact fluorescent or LED lamps between 20 and 55 watts. The lighting load can be installed at a distance of up to 1,000 feet from the LIGHTPOWER™ micro inverter. Observe all required AC
conductor sizing requirements. Ceiling T-Grid mount models approved for use in City of Chicago.
When normal utility supplied power is interrupted, the LIGHTPOWER™ Series unit will automatically transfer to emergency mode in less than 1-second and begin supplying pure sinusoidal AC power to the load for 90 minutes. The unit is capable of operating normally on, normally off, or switched loads. A low voltage battery disconnect circuit will prevent “deep discharge” damage to the battery. AC lockout prevents battery discharge prior to initial unit power-up. The charging circuit will bring the batteries to full recharge within UL time standards. A “brownout” circuit will automatically transfer the unit to emergency power if the utility voltage falls to a predetermined “low line” limit.